WAGO-I/O-SYSTEM 750 Connect Devices 43
750-652 Serial Interface RS-232 / RS-485
Manual
Version 1.3.0
7 Connect Devices
Use shielded signal lines!
Only use shielded signal lines for analog signals and I/O modules which are
equipped with shield clamps. Only then can you ensure that the accuracy and
interference immunity specified for the respective I/O module can be achieved
even in the presence of interference acting on the signal cable.
7.1 Connecting a Conductor to the CAGE CLAMP
®
The WAGO CAGE CLAMP
®
connection is appropriate for solid, stranded and
finely stranded conductors.
Only connect one conductor to each CAGE CLAMP
®
!
Only one conductor may be connected to each CAGE CLAMP
®
.
Do not connect more than one conductor at one single connection!
If more than one conductor must be routed to one connection, these must be
connected in an up-circuit wiring assembly, for example using WAGO feed-
through terminals.
Exception:
If it is unavoidable to jointly connect 2 conductors, then you must use a ferrule to
join the wires together. The following ferrules can be used:
Length: 8 mm
Nominal cross section
max.
: 1 mm
2
for 2 conductors with 0.5 mm
2
each
WAGO product: 216-103 or products with comparable properties
1. For opening the CAGE CLAMP
®
insert the actuating tool into the opening
above the connection.
2. Insert the conductor into the corresponding connection opening.
3. For closing the CAGE CLAMP
®
simply remove the tool. The conductor is
now clamped firmly in place.