7-5 Direct operation sample program
The following shows an example of direct operation on the X-axis using the settings below.
These parameters must be set before this ladder program is executed.
(1) Operation settings
X-axis target coordinate data: 100000 (pulses)
X-axis target speed data: 200000 (p/s)
X-axis acceleration speed No.: 00 (parameter 1 data)
X-axis deceleration speed No.: 00 (parameter 1 data)
Address A+0010 to 0013 of parameter 1: 20000 (reference speed)
Address A+0024 to 0027 of parameter 1: 5 (acceleration time)
Address A+0030 to 0033 of parameter 1: 10 (deceleration time)
Normally, at automatic I/O registration, the top address of the special I/O data area is 49000 and this
area is not handled as a relay.
For this reason, only the data that must be handled as a relay is transferred in advance to relay area
by a ladder program. (See item "Ladder.")
When numbers in the relay No. 7000 range are turned ON by this ladder program, direct operation is
executed.
20000
(P/S)
5(ms) 10(ms)
1000000(pulses)
When the reference speed is the same as the
target speed, the acceleration time and deceleration
time become the actual acceleration or deceleration
durations as they are.