Electrical Wiring
Connects the cable for power supply to TB1 on the rear side of ZM-
**
.
Wiring
7
Insulation transformer
or
Stabilized transformer
1.25mm
2
twisted
to ZM-72 Series/
ZM-82 Series
Power Supply
When TB1 is used for wiring, refer to the value as described above table.
The power source used must be within the allowable voltage fluctuation.
Use a power source with low noise between the cables or ground and the cable.
Use as thick a power cable as possible to minimize any drop in voltage.
Keep cables of 100V AC and 24V DC sufficiently away from high-voltage, large-current cables.
Notes on Usage of ZM-72 series/ZM-82 series (100 to 240 VAC specifications)
Generally, an isolating transformer improves noise resistance. However, if the display unit is far away
from the secondary port of the transformer and noise gets mixed in, an isolating transformer becomes
unnecessary.
If any power voltage fluctuation caused by noise is expected, it is recommended that a voltage stabilizer
be used.
Screw
Screw Size
M3.5ZM-42/43 Series, ZM-52D
Torque (N m)
Clamp Terminal (Unit : mm)
0.49
7.0MAX
7.0MAX
M3.5ZM-72 Series/ZM-82 Series 0.49
8.0MAX
8.0MAX
Type
DC 24V
(+)
(-)
TB1
Power supply
DC24V±10%
Earth
Power supply
100-200VAC
L
N
NC
TB1
Earth
CN2
CN1
MJ2 MJ1
DC24V
(+)
(-)
CN2
MJ1MJ2
C
N
1
100-
240VAC
L
N
NC
ZM-42/43 Series, ZM-52D
ZM-72 Series/ZM-82 Series
Type : AC100-200V
1 Wiring